Group Arrangement of WD90 Cable Boxes |
|
|
|
|
Possible group arrangements depend on the box size and the wall type. In general, there must be a 1.5 cm seam of mortar or plaster filling up the entire space between two cable boxes. It must fill up the entire space between the boxes inside the wall or ceiling. When a group is installed in a light partition wall it is also necessary to install a bolt above and below each box. If more than two boxes are installed in ceilings in front of one another, they must be screwed together with distance anchors.
| Possible Combinations for Group Arrangements Maximum Combinations with a Distance of 1.5cm A distance of more than 20cm is considered as a new group or a separate installation | | | Box Dimensions (HxW) | Possible Combinations | Buck Opening (HxW) | | Solid Wall | Up to 110x640mm | 4 boxes on top of each other, 3 boxes next to each other | 50x200cm | | Solid Wall | Up to 110x500mm | 7 boxes on top of each other, 3 boxes next to each other | 90x156cm | | Light Weight Wall | Up to 110x535mm | 6 boxes on top of each other, 3 boxes next to each other | Max. 605x535mm | | Ceiling | Up to 110x640mm | 3 boxes in front of one another, next to each other without any limitation | 40x ? cm | | Ceiling | Up to 110x640mm | in one row, in front of one another without any limitation | 66x ? cm |
|
|