English (United Kingdom)
Group Arrangement of WD90 Cable Boxes PDF Print E-mail

WD90 - Cable BoxesPossible group arrangements depend on the box size and the wall type.
In general, there must be a 1.5 cm seam of mortar or plaster filling up the entire space between two cable boxes. It must fill up the entire space between the boxes inside the wall or ceiling. When a group is installed in a light partition wall it is also necessary to install a bolt above and below each box. If more than two boxes are installed in ceilings in front of one another, they must be screwed together with distance anchors.

 

Possible Combinations for Group Arrangements

Maximum Combinations with a Distance of 1.5cm

A distance of more than 20cm is considered as a new group or a separate installation

 

Box Dimensions (HxW)

Possible Combinations

Buck Opening (HxW)

Solid Wall

Up to 110x640mm

4 boxes on top of each other,

3 boxes next to each other

50x200cm

Solid Wall

Up to 110x500mm

7 boxes on top of each other,

3 boxes next to each other

90x156cm

Light Weight Wall

Up to 110x535mm

6 boxes on top of each other,

3 boxes next to each other

Max. 605x535mm

Ceiling

Up to 110x640mm

3 boxes in front of one another,

next to each other without any limitation

40x ? cm

Ceiling

Up to 110x640mm

in one row, 

in front of one another without any limitation

66x ? cm